The Expert Community for Bathroom Remodeling

Oil paint GOST 14202 69. Pipelines of industrial enterprises

GOST 14202-69
Group G19

INTERSTATE STANDARD

PIPELINES OF INDUSTRIAL ENTERPRISES

Identification painting, warning signs and labels

Pipe lines of industrial plants. Identification colouring, safety signs and marking screens

ISS 23.040

Introduction date 1971-01-01

Decree of the Committee of Standards, Measures and measuring instruments under the Council of Ministers of the USSR of February 7, 1969 N 168, the deadline for introduction is set from 01.01.71

Reissue. March 2004

1. This standard applies to the identification coloring, warning signs and marking plates of pipelines (including fittings, fittings, fittings and insulation) at designed, newly built, reconstructed and existing industrial enterprises inside buildings, at outdoor installations and communications located on overpasses and in underground channels in order to quickly determine the contents of pipelines and facilitate the management of production processes, as well as ensuring labor safety.

The standard does not apply to the identification coloring of pipelines and ducts with electrical wiring.

2. The following ten enlarged groups of substances transported through pipelines are established:

1) water;

3) air;

4) combustible gases (including liquefied gases);

5) non-flammable gases (including liquefied gases);

6) acids;

7) alkalis;

8) combustible liquids;

9) non-flammable liquids;

0) other substances.

3. Identification coloring and digital designation of enlarged groups of pipelines must correspond to those indicated in Table 1.

Table 1

Substance being transported

Samples and name of colors of identification coloring

Group number

Name

Green

Red

combustible gases

Non-flammable gases

Orange

Violet

Flammable liquids

Brown

Non-flammable liquids

Other substances

4. Characteristics of colors of identification coloring should correspond to those specified in Appendix 1.

5. Fire-fighting pipelines, regardless of their contents (water, foam, steam for extinguishing a fire, etc.), sprinkler and deluge systems in the areas of shut-off and control valves and at the points of connection of hoses and other fire extinguishing devices must be painted red (signal).

If it is necessary to indicate the contents of fire-fighting pipelines, it is allowed to additionally designate them by means of marking plates painted in the appropriate distinctive colors.

6. Identification painting of pipelines should be carried out continuously over the entire surface of communications or in separate sections.

The method for performing identification painting should be selected depending on the location of the pipelines, their length, diameter, the number of lines located together, safety and industrial sanitation requirements, lighting conditions and visibility of pipelines for maintenance personnel and the general architectural solution.

It is recommended to paint pipelines in sections in workshops with a large number and great length communications, as well as in cases where, due to the increased requirements for color reproduction and the nature of the architectural solution of the interior, the concentration of bright colors is undesirable.

Identification painting over the entire surface of pipelines is recommended for use with a small length and a relatively small number of communications, if it does not worsen working conditions in the shops.

On outdoor installations, it is recommended to use identification coloring over the entire surface only in cases where this does not cause deterioration of operating conditions due to the effect of solar radiation on communications.

7. When applying identification coloring in sections to pipelines located inside industrial premises, it is recommended to paint the rest of the communications surface in the color of walls, partitions, ceilings and other interior elements against which the pipelines are located. At the same time, it is not allowed to paint pipelines between sections with an identification color adopted to designate other enlarged groups of substances.

8. When applying identification coloring in sections to pipelines located outside buildings, it is recommended to paint the rest of the communications surface in colors that help reduce the thermal effect of solar radiation on pipelines.

9. When laying communications in impassable channels and when laying communications without channels, areas of identification coloring on pipelines should be applied within the chambers and manholes.

10. Areas of identification coloring should be applied taking into account local conditions at the most critical communication points (at branches, at joints, flanges, at sampling and instrumentation points, at places where pipelines pass through walls, partitions, ceilings, at inputs and outputs from industrial buildings etc.) at least every 10 m inside production facilities and outdoor installations and every 30-60 m on external main routes.

11. The width of the areas of identification coloring should be taken depending on the outer diameter of the pipelines (including insulation):

for pipes with a diameter of up to 300 mm - at least four diameters;

for pipes with a diameter of more than 300 mm - at least two diameters.

With a larger number of parallel communications, it is recommended that the areas of identification coloration on all pipelines be of the same width and applied at the same intervals.

With large diameters of pipelines, areas of identification coloring may be applied in the form of strips with a height of at least 1/4 of the pipeline circumference.

The width of the strips must correspond to the dimensions established for pipelines of a given diameter.

12. To designate the most hazardous substances transported by properties, warning color rings should be applied to pipelines.

Identification colors for warning rings must correspond to those indicated in Table 2.

table 2

Signal color samples

Name of signal colors

Properties of the transported substance

Flammable, flammable and explosive

Hazard or hazard (poison, toxicity, asphyxiation, thermal or chemical burns, radioactivity, high pressure or deep vacuum, etc.)

Security or Neutrality

Notes:

1. When applying rings yellow color according to the identification coloring of pipelines of gases and acids, the rings must have black borders with a width of at least 10 mm.

2. When applying green rings for the identification color of water pipelines, the rings must have white borders with a width of at least 10 mm.

13. In cases where a substance simultaneously has several dangerous properties, indicated by different colors, rings of several colors should be applied to pipelines at the same time.

On vacuum pipelines, in addition to the distinctive color, it is necessary to give the inscription "vacuum".

14. According to the degree of danger to human life and health or the operation of the enterprise, substances transported through pipelines should be divided into three groups, indicated by the corresponding number of warning rings in accordance with Table 3.

Table 3

Number of warnings
rings

Substance being transported

Pressure in kgf/cm

Temperature in °C

superheated steam

250 to 350

Hot water, saturated steam

Superheated and saturated steam, hot water

120 to 250

Combustible (including liquefied and active gases, flammable and combustible liquids)

From minus 70 to 250


From minus 70 to 350

Two

superheated steam

350 to 450

Hot water, saturated steam

80 to 184

Products with toxic properties (except for highly toxic substances and fuming acids)

From minus 70 to 350

Combustible (including liquefied) active gases, flammable and combustible liquids

25 to 64

From 250 to 350 and from
minus 70 to 0

Non-flammable liquids and vapors, inert gases

64 to 100

From 340 to 450 and from minus 70 to 0

superheated steam

Regardless of the pressure

450 to 660

Hot water, saturated steam

Potent toxic substances (SDN) and fuming acids

Regardless of the pressure

From minus 70 to 700

Other products with toxic properties

From minus 70 to 700

Combustible (including liquefied) and active gases, flammable and combustible liquids

Regardless of the pressure

350 to 700

Non-flammable liquids and vapors, inert gases

Regardless of the pressure

450 to 700

Note. For substances that are dangerous in terms of properties or a combination of properties that are not included in this table, hazard groups should be established in agreement with the bodies of Gosgortekhnadzor.

15. Characteristics of signal colors must comply with those specified in Appendix 2.

16. The width of the warning rings and the distance between them must be taken depending on the outer diameter of the pipelines in accordance with Figure 1 and Table 4.

Damn.1. - Width of warning rings and distance between them

Table 4

Outer diameter (with insulation)

81 to 160

161 to 300

17. With a large number of parallel communications, warning rings on all pipelines should be of the same width and applied at the same intervals.

18. Gas outlet lines and venting to the atmosphere, depending on their contents, must have an identification color established for the symbolic designation of enlarged groups, with winding transverse rings of the corresponding signal color.

19. To designate pipelines with content that is especially hazardous to human health and life or the operation of an enterprise, as well as, if necessary, to specify the type of hazard, warning signs should be used in addition to color warning rings.

20. Warning signs should indicate the following substances: poisonous, flammable, explosive, radioactive, as well as other dangerous contents of pipelines (for example, substances that are hazardous when splashed, etc.).

21. Warning signs should be in the form of a triangle. Images must be black on a yellow background.

22. The image of warning signs should be taken in accordance with Figure 2 and Table 5.

Damn.2. - Image of warning signs

Table 5

Size options

23. In cases where the impact of aggressive flowing substances can cause a change in the hue of distinctive colors, pipelines should be marked with marking plates.

24. Labeling plates should be used to additionally indicate the type of substances and their parameters (temperature, pressure, etc.) required by the operating conditions. Marking plates on pipelines or on the surfaces of structures to which pipelines are attached must be marked with alphabetic or numeric inscriptions.

25. The inscriptions on the shields of the pipelines must be made in a clear, well-defined font and must not contain unnecessary data, little-used terms and incomprehensible abbreviations. The font for inscriptions is recommended to be taken in accordance with GOST 10807-78*.
________________
* Within the territory of Russian Federation GOST R 52290-2004 applies. - Database manufacturer's note.

It is allowed to designate the type of substance by means of numbers in accordance with Appendix 3.

Designation of the type of substance by chemical formulas not allowed.

26. The direction of the flow of substances transported through pipelines must be indicated by the sharp end of the marking plates or arrows applied directly to the pipelines.

The shape and size of the arrows must match the shape and size of the labels.

27. Marking shields must be of four types:

1 - to indicate the flow moving in both directions;

2 - the same, in the left direction;

3 - the same, in the right direction;

4 - to indicate the place of selection of the transported substance.

28. The dimensions of the marking plates must correspond to those indicated in Fig. 3 and in Table 6.

Damn.3. - Dimensions of labels

Table 6

Size options

Letter height

one line

two lines

29. Size options for labels, inscriptions and warning signs should be used mainly:

1 - in laboratories;

2 and 3 - in industrial premises;

4 and 5 - on outdoor installations and outdoor main routes.

30. When attaching them to pipelines, warning signs should be placed together with marking plates.

31. The height of markings on pipelines should be taken depending on the outer diameter of the pipeline in accordance with Figure 4 and Table 7.

Damn.4. - Height of markings on pipelines

Table 7

Size options

Outside diameter

Letter height

One line

Two lines

81 to 160

161 to 220

221 to 300

The color of markings and arrows indicating the direction of flow applied to pipelines and marking plates should be white or black, taking into account the greatest contrast with the main color of the pipelines.

The color of the inscriptions when applied against the background of identification coloring is taken:

white - on a green, red and brown background;

black - on a blue, yellow, orange, purple and gray background.

32. The size of labels, inscriptions and warning signs should be selected depending on the distance from which they should be perceived by personnel associated with the operation of pipelines in accordance with Figure 5 and Table 8.

Damn.5. - Size of labels, inscriptions and warning signs

Table 8

Distance from the observer in m

6 to 12

12 to 18

18 to 24

Over 24

33. Paint and varnish coatings for identification painting, marking plates and warning signs must be carried out in accordance with the current standards for paintwork materials and coatings, depending on the material of pipelines or the insulation protecting them and operating conditions, as well as the cost of paint and varnish coatings and the technology of their application.

34. Paints and varnishes used for identification painting, labeling plates and warning signs must meet the requirements of the relevant standards, as well as technical documentation approved in the prescribed manner.

35. When preparing surfaces for painting, applying and drying paint and varnish coatings, the safety regulations and fire prevention measures provided for by the current fire regulations and rules must be observed.

36. In heated and ventilated industrial premises without aggressive environments, it is recommended to carry out the identification coloring of pipelines, marking plates and warning signs with pentaphthalic enamels of grades PF-115 according to GOST 6465-76, PF-133 according to GOST 926-82 and other brands according to the technical documentation approved according to established order.

It is recommended to paint fire-fighting pipelines and equipment with red enamel according to the technical documentation approved in the prescribed manner.

37. Identification colors and signal colors are allowed to be accepted in accordance with the following standards of the color standard card index: green N 343-344; red N 10-11; blue N 423-424; yellow N 205-206; orange N 101-102; violet N 505-506; brown N 647-648; gray N 894-895. Required shades of purple and brown in accordance with the samples of Table 1 can be obtained by adding white paint.

38. The identification coloring of pipelines and the color finish of marking plates and warning signs should be periodically renewed, taking into account the provision of clear visibility of colors, images and inscriptions. The coloring should be even, without streaks, wrinkles, spots and should not peel off.

39. Marking boards, inscriptions and warning signs should be located taking into account local conditions at the most critical communication points (at branches, at junctions, at points of selection, at valves, gate valves, valves, gates, control devices, at places where pipelines pass through walls , partitions, ceilings, at inputs and outputs from industrial buildings, etc.).

Marking plates, warning signs and inscriptions on pipelines should be located in well-lit places or illuminated to ensure their clear visibility, while light sources should not obscure the images and inscriptions, as well as dazzle personnel when observing them.

It is recommended to take the lowest illumination at critical communication points with marking plates, inscriptions and warning signs in them at 150 lux with fluorescent lamps and 50 lux with incandescent lamps.

40. In all industrial premises where there are pipelines, in places that are well accessible for viewing, identification coloring schemes for communications should be hung out with a decoding of the distinctive colors, warning signs and digital designations adopted for marking pipelines.

ATTACHMENT 1

ATTACHMENT 1

distinctive color

Chromaticity coordinates
(for source C)

Reflection coefficient, %

y>0.1x+0.412

y>2.8x-0.552
y<0,474-0,1x
x>0.357-0.15y

at<0,290+0,08x

y>0.920-x

y>0.559-0.394x

y>0.316

y<0,550-x

y<0,64x+0,118

y>0.994-3x

y>0.94x+0.024

y>0.084-1.07x

y>0.77x+0.075

y<0,823-0,94x

y

Orange

at<0,204+0,362x

x>0.669-0.26y

Violet

y<0,17x+0,223

y>0.25x+0.185

y>7x-1.854

Brown

x>0.545-0.35y

y>0.19x+0.257

x<0,588-0,25y

y<0,39x+0,195


APPENDIX 2


signal color

Chromaticity coordinates
(for source C)

Reflection coefficient, %

y<0,290+0,080x

y>0.920-x
y>0.559-0.394x
y>0.316

x>0.048+0.827y

y>0.120+0.632x

y>0.887-x

x>0.526-0.683y

x<0,410-0,317y

y>0.282+0.396x

y<0,547-0,394x

APPENDIX 3

Numerical designations

The substance being transported. Name

Water

drinking

technical

hot (water supply)

hot (heating)

nutritious

reserve

reserve

condensate

other types of water

waste, waste

Steam

low pressure (up to 2 kgf/cm)

saturated

overheated

heating

wet (juice)

selective

reserve

vacuum

other types of steam

spent

Air

atmospheric

conditioned

circulation

hot

compressed

pneumatic transport

oxygen

vacuum

other types of air

spent

combustible gases

luminous

generator

acetylene

ammonia

hydrogen and gases containing it

hydrocarbons and their derivatives

carbon monoxide and gases containing it

reserve

other types of combustible gases

waste combustible gases

Non-flammable gases

nitrogen and gases containing it

reserve

chlorine and gases containing it

carbon dioxide and gases containing it

inert gases

sulfur dioxide and gases containing it

reserve

reserve

other types of non-flammable gases

waste non-combustible gases

acids
sulfuric
hydrochloric
nitric
reserve
inorganic acids and their solutions
organic acids and their solutions
acid salt solutions
reserve
other acid reaction liquids
waste acids and acidic effluents (at pH<6,5)
alkalis

sodium

potash

calcareous

lime water

inorganic alkalis and their solutions

organic alkalis and their solutions

reserve

reserve

other alkaline liquids

spent alkalis and alkaline effluents (рН>8.5)

Flammable liquids

category A fluids (<28 °С)

category B liquids (>28 °С<120 °С)*

_______________
* Corresponds to the original. - Database manufacturer's note.

category B fluids (> 120 °C)

lubricating oils

other organic flammable liquids

explosive liquids

reserve

reserve

other flammable liquids

combustible drains

Non-flammable liquids

liquid food products

aqueous solutions (neutral)

other solutions (neutral)

aqueous suspensions

other suspensions

emulsions

reserve

reserve

other non-flammable liquids

non-combustible drains (neutral)

Other substances

powder materials

bulk materials granular

mixtures of solid materials with air

water pulps

pulps of other liquids

reserve

reserve

reserve

waste hard materials

Note. If necessary, each of the subgroups can be divided into ten smaller subdivisions, indicated by the third character of the digital designation (for example, in the enlarged group 4 "Combustible gases" as part of subgroup 6 "Hydrocarbons and their derivatives", ethylene can be distinguished by the third character - 4.61 ).

REFERENCE APPENDIX TO GOST 14202-69. Examples of performing identification painting of pipelines

Examples of performing identification painting of pipelines

Sulphuric acid
Potash alkalis
Hot water for water supply
Superheated steam 450 °C


Compressed air
Leaded gasoline
Ethylene
air vacuum
atmospheric air
Gas outlet line

Water for fire fighting

Note: On hot water and leaded petrol pipes, the inscriptions on the distinctive belts must be white.

STATE STANDARD OF THE UNION OF THE SSR

PIPELINES OF INDUSTRIAL ENTERPRISES

IDENTIFICATION COLOR WARNING
SIGNS AND LABELS

GOST 14202-69

USSR STATE COMMITTEE ON STANDARDS

Moscow

STATE STANDARD OF THE UNION OF THE SSR

By the Decree of the Committee of Standards, Measures and Measuring Instruments under the Council of Ministers of the USSR dated February 7, 1969 No. 168, the introduction period was established

from 01.01.71

Non-compliance with the standard is punishable by law

1. This standard applies to identification coloring, warning signs and marking plates of pipelines (including fittings, fittings, fittings and insulation) for designed, newly built, reconstructed and existing industrial enterprises inside buildings, for outdoor installations and communications located on overpasses and in underground channels in order to quickly determine the contents of pipelines and facilitate the management of production processes, as well as ensuring labor safety.

The standard does not apply to the identification coloring of pipelines and ducts with electrical wiring.

2. The following ten enlarged groups of substances transported through pipelines are established:

1) water;

2) steam;

3) air;

4) combustible gases (including liquefied gases);

5) non-flammable gases (including liquefied gases);

6) acids;

7) alkalis;

8) combustible liquids;

9) non-flammable liquids;

10) other substances.

3. Identification coloring and digital designation of enlarged groups of pipelines must comply with those specified in.

4. The characteristics of the colors of the identification color must correspond to those specified in.

5. Fire-fighting pipelines, regardless of their contents (water, foam, steam for extinguishing a fire, etc.), sprinkler and deluge systems in the areas of shut-off and control valves and at the points of connection of hoses and other fire extinguishing devices must be painted red (signal).

If it is necessary to indicate the contents of fire-fighting pipelines, it is allowed to additionally designate them by means of marking plates painted in the appropriate distinctive colors.

13. In cases where a substance simultaneously has several dangerous properties, indicated by different colors, rings of several colors should be applied to pipelines at the same time.

On vacuum pipelines, in addition to the distinctive color, it is necessary to give the inscription "vacuum".

14. According to the degree of danger to human life and health or the operation of the enterprise, substances transported through pipelines should be divided into three groups, indicated by the appropriate number of warning rings in accordance with.

15. Characteristics of signal colors must comply with those specified in.

16. The width of the warning rings and the distance between them must be taken depending on the outer diameter of the pipelines in accordance with and.

17. With a large number of parallel communications, warning rings on all pipelines should be of the same width and applied at the same intervals.

Table 2

Signal color samples

Name of signal colors

Properties of the transported substance

Red

Flammable, flammable and explosive

Yellow

Danger or harmfulness (poison, toxicity, ability to cause asphyxiation, thermal or chemical burns, radioactivity, high pressure or deep vacuum, etc.)

Green

Security or Neutrality

Notes:

1. When applying yellow rings for identification coloring of pipelines of gases and acids, the rings must have black borders with a width of at least 10 mm.

2. When applying green rings for the identification color of water pipelines, the rings must have white borders with a width of at least 10 mm.

18. Gas outlet lines and venting to the atmosphere, depending on their contents, must have an identification color established for the symbolic designation of enlarged groups, with winding transverse rings of the corresponding signal color.

19. To designate pipelines with content that is especially hazardous to human health and life or the operation of an enterprise, as well as, if necessary, to specify the type of hazard, warning signs should be used in addition to color warning rings.

20. Warning signs should indicate the following substances: poisonous, flammable, explosive, radioactive, as well as other dangerous contents of pipelines (for example, substances that are hazardous when splashed, etc.).

21. Warning signs should be in the form of a triangle. Images must be black on a yellow background.

Toxic substances

Flammable substances

radioactive substances

Explosives

Other hazards

Crap. 2

It is allowed to designate the type of substance by means of numbers in accordance with. The designation of the type of substance by means of chemical formulas is not allowed.

26. The direction of the flow of substances transported through pipelines should be indicated by the sharp end of the marking plates or arrows applied directly to the pipelines.

The shape and size of the arrows must match the shape and size of the labels.

27. Marking shields must be of four types:

1 - to indicate the flow moving in both directions;

2 - the same, in the left direction;

3 - the same, in the right direction;

4 - to indicate the place of selection of the transported substance.

28. The dimensions of the camouflage shields must correspond to those indicated on and in.


Crap. four

33. Paint and varnish coatings for identification painting, marking plates and warning signs must be carried out in accordance with the current standards for paintwork materials and coatings, depending on the material of pipelines or the insulation protecting them and operating conditions, as well as the cost of paint and varnish coatings and the technology of their application.

34. Paints and varnishes used for identification painting, marking plates and warning signs must meet the requirements of the relevant standards, as well as technical documentation approved in the prescribed manner.

35. When preparing surfaces for painting, applying and drying paint and varnish coatings, the safety regulations and fire prevention measures provided for by the current fire regulations and rules must be observed.

36. In heated and ventilated industrial premises without aggressive environments, it is recommended to carry out the identification coloring of pipelines, marking plates and warning signs with pentaphthalic enamels of grades PF-115 according to GOST 6465-76, PF-133 according to GOST 926-82 and other brands according to the technical documentation approved according to established order.

It is recommended to paint fire-fighting pipelines and equipment with red enamel according to the technical documentation approved in the prescribed manner.

37. Identification colors and signal colors are allowed to be accepted in accordance with the following standards of the color standard card index: green No. 343-344; red #10-11; blue #423-424; yellow #205-206; orange #101-102; purple #505-506; brown #647-648; gray #894-895. The desired shades of purple and brown according to the samples can be obtained by adding white paint.

38. The identification coloring of pipelines and the color finish of marking plates and warning signs should be periodically renewed, taking into account the provision of clear visibility of colors, images and inscriptions. The coloring should be even, without streaks, wrinkles, spots and should not peel off.

39. Marking boards, inscriptions and warning signs should be located taking into account local conditions at the most critical communication points (at branches, at junctions, at points of selection, at valves, gate valves, valves, gates, control devices, at places where pipelines pass through walls , partitions, ceilings, at inputs and outputs from industrial buildings, etc.).

Marking plates, warning signs and inscriptions on pipelines should be located in well-lit places or illuminated to ensure their clear visibility, while light sources should not obscure the images and inscriptions, as well as dazzle personnel when observing them.


Crap. 5

Table 8

It is recommended to take the lowest illumination at critical points of communication when labeling plates, inscriptions and warning signs are located in them at 150 lux with fluorescent lamps and 50 lux with incandescent lamps.

40. In all industrial premises where there are pipelines, in places that are well accessible for viewing, identification coloring schemes for communications should be hung out with a decoding of the distinctive colors, warning signs and digital designations adopted for marking pipelines.

ATTACHMENT 1

distinctive color

Reflection coefficient %

Green

y>0.1x +0.412

y>2.8x-0.552

at<0,474-0,1х

x>0.357-0.15y

9-17

Red

at<0,290+0,08х

y>0.920-x

y>0.559-0.394x

y>0.316

7-15

Blue

y<0,550- x

at<0,64х+0,118

Y>0.994-3x

y>0.94x+0.024

36-50

Yellow

y>0.084-1.07x

y>0.77х+0.075

y<0,823-0,94 x

y<х+0,006

30-45

Orange

y>0.380

y<0,204+0,362 x

x>0.669-0.26y

22-29

Violet

at<0,17х+0,223

at<2,6х-0,49

y>0.25x+0.185

y>7x-1.854

36-50

Brown

x>0.545-0.35y

y>0.19x+0.257

x<0,588-0,25у

at<0.39х+0,195

9-17

Grey

50-62

APPENDIX 2

signal color

Chromaticity coordinates (for source C)

Reflection coefficient %

Red

at<0,290+0,080 x

y >0.920's

y>0.559-0.394x

y>0.316

7-15

Yellow

x>0.048+0.827y

y>0.120+0.632x

y>0.887-x

over 45

Green

x>0.526-0.683y

x<0,410-0,317у

y>0.282+0.396x

at<0,547-0,394 x

15-30

APPENDIX 3

Numerical designations

Substance being transported

Name

Water

drinking

technical

hot (water supply)

hot (heating)

nutritious

reserve

reserve

condensate

other types of water

waste, waste

Steam

low pressure (up to 2 kgf / cm 2)

saturated

overheated

heating

wet (juice)

selective

reserve

vacuum

other types of steam

spent

Air

atmospheric

conditioned

circulation

hot

compressed

pneumatic transport

oxygen

vacuum

other types of air

spent

combustible gases

luminous

generator

acetylene

ammonia

hydrogen and gases containing it

hydrocarbons and their derivatives

carbon monoxide and gases containing it

reserve

other types of combustible gases

waste combustible gases

Non-flammable gases

nitrogen and gases containing it

reserve

chlorine and gases containing it

carbon dioxide and gases containing it

inert gases

sulfur dioxide and gases containing it

reserve

reserve

other types of non-flammable gases

waste non-combustible gases

acids

sulfuric

hydrochloric

nitric

reserve

inorganic acids and their solutions

organic acids and their solutions

acid salt solutions

reserve

other acid reaction liquids

waste acids and acidic effluents (at pH<6,5)

alkalis

sodium

potash

calcareous

lime water

inorganic alkalis and their solutions

organic alkalis and their solutions

reserve

reserve

other alkaline liquids

7.Yu

spent alkalis and alkaline effluents (рН>8.5)

Flammable liquids

lubricating oils

other organic flammable liquids

explosive liquids

reserve

reserve

other flammable liquids

combustible drains

Non-flammable liquids

liquid food products

aqueous solutions (neutral)

other solutions (neutral)

aqueous suspensions

other suspensions

emulsions

reserve

reserve

other non-flammable liquids

non-combustible drains (neutral)

Other substances

powder materials

bulk materials granular

mixtures of solid materials with air

gels

water pulps

pulps of other liquids

reserve

reserve

reserve

waste hard materials

Note . If necessary, each of the subgroups can be divided into ten smaller subdivisions, indicated by the third character of the digital designation (for example, in the enlarged group 4 "Combustible gases" as part of subgroup 6 "Hydrocarbons and their derivatives", ethylene can be distinguished by the third character - 4.61 ).

REFERENCE APPENDIX TO GOST 14202-69

Examples of performing identification painting of pipelines

Sulphuric acid

Potash alkalis

Hot water for water supply

Steam superheated 450°C


Compressed air

Leaded gasoline

Ethylene

air vacuum

atmospheric air

Gas outlet line

Water for fire fighting

Note : Hot water and leaded petrol pipes must have white markings on the identification bands.

The standard applies to the identification coloring, warning signs and marking plates of pipelines (including connecting parts, fittings, fittings and insulation) at designed, newly built, reconstructed and existing industrial enterprises inside buildings, at outdoor installations and communications located on overpasses or in underground channels in order to quickly determine the contents of pipelines and facilitate the management of production processes, as well as ensuring labor safety. The standard does not apply to the identification coloring of pipelines and ducts with electrical wiring.

Designation: GOST 14202-69
Russian name: Pipelines of industrial enterprises. Identification painting, warning signs and labels
Status: valid
Text update date: 05.05.2017
Date added to database: 01.09.2013
Date of entry into force: 01.01.1971
Approved: 02/07/1969 USSR State Standard (USSR Gosstandart 168)
Published: Standards Publishing House (1987) IPK Standards Publishing House (2001)
Download links:

GOST 14202-69

INTERSTATE STANDARD

PIPELINES OF INDUSTRIAL
ENTERPRISES

IDENTIFICATION COLORATION, WARNING SIGNS
AND MARKING PLATES

STANDARDS PUBLISHING HOUSE
Moscow

INTERSTATE STANDARD

Reissue. September 2001

By the Decree of the Committee of Standards, Measures and Measuring Instruments under the Council of Ministers of the USSR dated February 7, 1969 No. 168, the introduction period was established

from 01.01.71

1. This standard applies to identification coloring, warning signs and marking plates of pipelines (including fittings, fittings, fittings and insulation) for designed, newly built, reconstructed and existing industrial enterprises inside buildings, for outdoor installations and communications located on overpasses and in underground channels in order to quickly determine the contents of pipelines and facilitate the management of production processes, as well as ensuring labor safety.

The standard does not apply to the identification coloring of pipelines and ducts with electrical wiring.

2. The following ten enlarged groups of substances transported through pipelines are established:

1) water;

2) steam;

3) air;

4) combustible gases (including liquefied gases);

5) non-flammable gases (including liquefied gases);

6) acids;

7) alkalis;

8) combustible liquids;

9) non-flammable liquids;

0) other substances.

3. Identification coloring and digital designation of enlarged groups of pipelines must correspond to those indicated in Table. .

4. The characteristics of the colors of identification coloring must correspond to those specified in the appendix.

5. Fire-fighting pipelines, regardless of their contents (water, foam, steam for extinguishing a fire, etc.), sprinkler and deluge systems in the areas of shut-off and control valves and at the points of connection of hoses and other fire extinguishing devices must be painted red (signal).

If it is necessary to indicate the contents of fire-fighting pipelines, it is allowed to additionally designate them by means of marking plates painted in the appropriate distinctive colors.

6. Identification painting of pipelines should be carried out continuously over the entire surface of communications or in separate sections.

The method of performing identification painting should be selected depending on the location of the pipelines, their length, diameter, the number of lines located together, safety and industrial hygiene requirements, lighting conditions and visibility of pipelines for maintenance personnel and general architectural solution.

Table 2

Signal color samples

Name of signal colors

Properties of the transported substance

Red

Flammable, flammable and explosive

Yellow

Danger or harmfulness (poison, toxicity, ability to cause asphyxiation, thermal or chemical burns, radioactivity, high pressure or deep vacuum, etc.)

Green

Security or Neutrality

Notes:

1. When applying yellow rings for identification coloring of pipelines of gases and acids, the rings must have black borders with a width of at least 10 mm.

2. When applying green rings for the identification color of water pipelines, the rings must have white borders with a width of at least 10 mm.

13. In cases where a substance simultaneously has several dangerous properties, indicated by different colors, rings of several colors should be applied to pipelines at the same time.

On vacuum pipelines, in addition to the distinctive color, it is necessary to give the inscription "vacuum".

14. According to the degree of danger to human life and health or the operation of the enterprise, substances transported through pipelines should be divided into three groups, indicated by the corresponding number of warning rings in accordance with Table. .

16. The width of the warning rings and the distance between them must be taken depending on the outer diameter of the pipelines in accordance with drawing. and tab. .

Crap. 5

Table 8

33. Paint and varnish coatings for identification painting, marking plates and warning signs must be carried out in accordance with the current standards for paintwork materials and coatings, depending on the material of pipelines or the insulation protecting them and operating conditions, as well as the cost of paint and varnish coatings and the technology of their application.

34. Paints and varnishes used for identification painting, marking plates and warning signs must meet the requirements of the relevant standards, as well as technical documentation approved in the prescribed manner.

35. When preparing surfaces for painting, applying and drying paint and varnish coatings, the safety regulations and fire prevention measures provided for by the current fire regulations and rules must be observed.

36. In heated and ventilated industrial premises without aggressive environments, it is recommended to carry out the identification coloring of pipelines, marking plates and warning signs with pentaphthalic enamels of grades PF-115 according to GOST 6465-76, PF-133 according to GOST 926-82 and other brands according to the technical documentation approved according to established order.

It is recommended to paint fire-fighting pipelines and equipment with red enamel according to the technical documentation approved in the prescribed manner.

37. Identification colors and signal colors are allowed to be accepted in accordance with the following standards of the color standard card index: green No. 343-344; red #10-11; blue #423-424; yellow #205-206; orange #101-102; purple #505-506; brown #647-648; gray #894-895. Required shades of purple and brown in accordance with the samples of Table. can be obtained by adding white paint.

38. The identification coloring of pipelines and the color finish of marking plates and warning signs should be periodically renewed, taking into account the provision of clear visibility of colors, images and inscriptions. The coloring should be even, without streaks, wrinkles, spots and should not peel off.

39. Marking boards, inscriptions and warning signs should be located taking into account local conditions at the most critical communication points (at branches, at junctions, at points of selection, at valves, gate valves, valves, gates, control devices, at places where pipelines pass through walls , partitions, ceilings, at inputs and outputs from industrial buildings, etc.).

Marking plates, warning signs and inscriptions on pipelines should be located in well-lit places or illuminated to ensure their clear visibility, while light sources should not obscure the images and inscriptions, as well as dazzle personnel when observing them.

It is recommended to take the lowest illumination at critical points of communication when labeling plates, inscriptions and warning signs are located in them at 150 lux with fluorescent lamps and 50 lux with incandescent lamps.

40. In all industrial premises where there are pipelines, in places that are well accessible for viewing, identification coloring schemes for communications should be hung out with a decoding of the distinctive colors, warning signs and digital designations adopted for marking pipelines.

ATTACHMENT 1

distinctive color

Reflection coefficient %

distinctive color

Chromaticity coordinates (for source C)

Reflection coefficient %

Green

y>0.1x +0.412

y>2.8x-0.552

at<0,474-0,1х

x>0.357-0.15y

Orange

y>0.380

y<0,204+0,362x

x>0.669-0.26y

Red

at<0,290+0,08х

y>0.920-x

y>0.559-0.394x

y>0.316

Violet

at<0,17х+0,223

at<2,6х-0,49

y>0.25x+0.185

y>7x-1.854

Blue

y<0,550-x

at<0,64х+0,118

Y>0.994-3x

y>0.94x+0.024

Brown

x>0.545-0.35y

y>0.19x+0.257

x<0,588-0,25у

at<0.39х+0,195

Yellow

y>0.084-1.07x

y>0.77х+0.075

y<0,823-0,94x

y<х+0,006

Grey

APPENDIX 2

signal color

Chromaticity coordinates (for source C)

Reflection coefficient %

Red

at<0,290+0,080x

y>0.920's

y>0.559-0.394x

y>0.316

Yellow

x>0.048+0.827y

y>0.120+0.632x

y>0.887-x

over 45

Green

x>0.526-0.683y

x<0,410-0,317у

y>0.282+0.396x

at<0,547-0,394x

APPENDIX 3

Numerical designations

Substance being transported

Name

drinking

technical

hot (water supply)

hot (heating)

nutritious

condensate

other types of water

waste, waste

low pressure (up to 2 kgf / cm 2)

saturated

overheated

heating

wet (juice)

selective

vacuum

other types of steam

spent

atmospheric

conditioned

circulation

pneumatic transport

oxygen

other types of air

spent

combustible gases

luminous

generator

acetylene

hydrogen and gases containing it

hydrocarbons and their derivatives

carbon monoxide and gases containing it

other types of combustible gases

waste combustible gases

Non-flammable gases

nitrogen and gases containing it

chlorine and gases containing it

carbon dioxide and gases containing it

inert gases

sulfur dioxide and gases containing it

other types of non-flammable gases

waste non-combustible gases

inorganic acids and their solutions

organic acids and their solutions

acid salt solutions

other acid reaction liquids

waste acids and acidic effluents (at pH<6,5)

sodium

potash

calcareous

lime water

inorganic alkalis and their solutions

organic alkalis and their solutions

other alkaline liquids

spent alkalis and alkaline effluents (рН>8.5)

Flammable liquids

lubricating oils

other organic flammable liquids

explosive liquids

other flammable liquids

combustible drains

Non-flammable liquids

liquid food products

aqueous solutions (neutral)

other solutions (neutral)

aqueous suspensions

other suspensions

emulsions

other non-flammable liquids

non-combustible drains (neutral)

Other substances

powder materials

bulk materials granular

mixtures of solid materials with air

water pulps

pulps of other liquids

waste hard materials

Note. If necessary, each of the subgroups can be divided into ten smaller subdivisions, indicated by the third character of the digital designation (for example, in the enlarged group 4 "Combustible gases" as part of subgroup 6 "Hydrocarbons and their derivatives", ethylene can be distinguished by the third character - 4.61 ).

Compressed air

Leaded gasoline

Ethylene

air vacuum

atmospheric air

Gas outlet line

Water for fire fighting

Note : Hot water and leaded petrol pipes must have white markings on the identification bands.

GOST 14202-69
Group G19

INTERSTATE STANDARD

PIPELINES OF INDUSTRIAL ENTERPRISES

Identification painting, warning signs and labels

Pipe lines of industrial plants. Identification colouring, safety signs and marking screens

ISS 23.040

Introduction date 1971-01-01

By the Decree of the Committee of Standards, Measures and Measuring Instruments under the Council of Ministers of the USSR of February 7, 1969 N 168, the introduction date was set from 01.01.71

Reissue. March 2004

1. This standard applies to the identification coloring, warning signs and marking plates of pipelines (including fittings, fittings, fittings and insulation) at designed, newly built, reconstructed and existing industrial enterprises inside buildings, at outdoor installations and communications located on overpasses and in underground channels in order to quickly determine the contents of pipelines and facilitate the management of production processes, as well as ensuring labor safety.

The standard does not apply to the identification coloring of pipelines and ducts with electrical wiring.

2. The following ten enlarged groups of substances transported through pipelines are established:

1) water;

3) air;

4) combustible gases (including liquefied gases);

5) non-flammable gases (including liquefied gases);

6) acids;

7) alkalis;

8) combustible liquids;

9) non-flammable liquids;

0) other substances.

3. Identification coloring and digital designation of enlarged groups of pipelines must correspond to those indicated in Table 1.

Table 1

Substance being transported

Samples and name of colors of identification coloring

Group number

Name

Green

Red

combustible gases

Non-flammable gases

Orange

Violet

Flammable liquids

Brown

Non-flammable liquids

Other substances

4. Characteristics of colors of identification coloring should correspond to those specified in Appendix 1.

5. Fire-fighting pipelines, regardless of their contents (water, foam, steam for extinguishing a fire, etc.), sprinkler and deluge systems in the areas of shut-off and control valves and at the points of connection of hoses and other fire extinguishing devices must be painted red (signal).

If it is necessary to indicate the contents of fire-fighting pipelines, it is allowed to additionally designate them by means of marking plates painted in the appropriate distinctive colors.

6. Identification painting of pipelines should be carried out continuously over the entire surface of communications or in separate sections.

The method for performing identification painting should be selected depending on the location of the pipelines, their length, diameter, the number of lines located together, safety and industrial sanitation requirements, lighting conditions and visibility of pipelines for maintenance personnel and the general architectural solution.

It is recommended to paint pipelines in sections in workshops with a large number and length of communications, as well as in cases where, due to the increased requirements for color rendering and the nature of the architectural solution of the interior, a concentration of bright colors is undesirable due to working conditions.

Identification painting over the entire surface of pipelines is recommended for use with a small length and a relatively small number of communications, if it does not worsen working conditions in the shops.

On outdoor installations, it is recommended to use identification coloring over the entire surface only in cases where this does not cause deterioration of operating conditions due to the effect of solar radiation on communications.

7. When applying identification coloring in sections to pipelines located inside industrial premises, it is recommended to paint the rest of the communications surface in the color of walls, partitions, ceilings and other interior elements against which the pipelines are located. At the same time, it is not allowed to paint pipelines between sections with an identification color adopted to designate other enlarged groups of substances.

8. When applying identification coloring in sections to pipelines located outside buildings, it is recommended to paint the rest of the communications surface in colors that help reduce the thermal effect of solar radiation on pipelines.

9. When laying communications in impassable channels and when laying communications without channels, areas of identification coloring on pipelines should be applied within the chambers and manholes.

10. Areas of identification coloring should be applied taking into account local conditions at the most critical communication points (at branches, at joints, flanges, at sampling and instrumentation points, at places where pipelines pass through walls, partitions, ceilings, at inputs and outputs from industrial buildings etc.) at least every 10 m inside production facilities and outdoor installations and every 30-60 m on external main routes.

11. The width of the areas of identification coloring should be taken depending on the outer diameter of the pipelines (including insulation):

for pipes with a diameter of up to 300 mm - at least four diameters;

for pipes with a diameter of more than 300 mm - at least two diameters.

With a larger number of parallel communications, it is recommended that the areas of identification coloration on all pipelines be of the same width and applied at the same intervals.

With large diameters of pipelines, areas of identification coloring may be applied in the form of strips with a height of at least 1/4 of the pipeline circumference.

The width of the strips must correspond to the dimensions established for pipelines of a given diameter.

12. To designate the most hazardous substances transported by properties, warning color rings should be applied to pipelines.

Identification colors for warning rings must correspond to those indicated in Table 2.

table 2

Signal color samples

Name of signal colors

Properties of the transported substance

Flammable, flammable and explosive

Danger or harmfulness (poison, toxicity, ability to cause asphyxiation, thermal or chemical burns, radioactivity, high pressure or deep vacuum, etc.)

Security or Neutrality

Notes:

1. When applying yellow rings for identification coloring of pipelines of gases and acids, the rings must have black borders with a width of at least 10 mm.

2. When applying green rings for the identification color of water pipelines, the rings must have white borders with a width of at least 10 mm.

13. In cases where a substance simultaneously has several dangerous properties, indicated by different colors, rings of several colors should be applied to pipelines at the same time.

On vacuum pipelines, in addition to the distinctive color, it is necessary to give the inscription "vacuum".

14. According to the degree of danger to human life and health or the operation of the enterprise, substances transported through pipelines should be divided into three groups, indicated by the corresponding number of warning rings in accordance with Table 3.

Table 3

Number of warnings
rings

Substance being transported

Pressure in kgf/cm

Temperature in °C

superheated steam

250 to 350

Hot water, saturated steam

Superheated and saturated steam, hot water

120 to 250

Combustible (including liquefied and active gases, flammable and combustible liquids)

From minus 70 to 250


From minus 70 to 350

Two

superheated steam

350 to 450

Hot water, saturated steam

80 to 184

Products with toxic properties (except for highly toxic substances and fuming acids)

From minus 70 to 350

Combustible (including liquefied) active gases, flammable and combustible liquids

25 to 64

From 250 to 350 and from
minus 70 to 0

Non-flammable liquids and vapors, inert gases

64 to 100

From 340 to 450 and from minus 70 to 0

superheated steam

Regardless of the pressure

450 to 660

Hot water, saturated steam

Potent toxic substances (SDN) and fuming acids

Regardless of the pressure

From minus 70 to 700

Other products with toxic properties

From minus 70 to 700

Combustible (including liquefied) and active gases, flammable and combustible liquids

Regardless of the pressure

350 to 700

Non-flammable liquids and vapors, inert gases

Regardless of the pressure

450 to 700

Note. For substances that are hazardous in terms of properties or a combination of properties that are not included in this table, hazard groups should be established in agreement with the Gosgortekhnadzor authorities.

15. Characteristics of signal colors must comply with those specified in Appendix 2.

16. The width of the warning rings and the distance between them must be taken depending on the outer diameter of the pipelines in accordance with Figure 1 and Table 4.

Damn.1. - Width of warning rings and distance between them

Table 4

Outer diameter (with insulation)

81 to 160

161 to 300

17. With a large number of parallel communications, warning rings on all pipelines should be of the same width and applied at the same intervals.

18. Gas outlet lines and venting to the atmosphere, depending on their contents, must have an identification color established for the symbolic designation of enlarged groups, with winding transverse rings of the corresponding signal color.

19. To designate pipelines with content that is especially hazardous to human health and life or the operation of an enterprise, as well as, if necessary, to specify the type of hazard, warning signs should be used in addition to color warning rings.

20. Warning signs should indicate the following substances: poisonous, flammable, explosive, radioactive, as well as other dangerous contents of pipelines (for example, substances that are hazardous when splashed, etc.).

21. Warning signs should be in the form of a triangle. Images must be black on a yellow background.

22. The image of warning signs should be taken in accordance with Figure 2 and Table 5.

Damn.2. - Image of warning signs

Table 5

Size options

23. In cases where the impact of aggressive flowing substances can cause a change in the hue of distinctive colors, pipelines should be marked with marking plates.

24. Labeling plates should be used to additionally indicate the type of substances and their parameters (temperature, pressure, etc.) required by the operating conditions. Marking plates on pipelines or on the surfaces of structures to which pipelines are attached must be marked with alphabetic or numeric inscriptions.

25. The inscriptions on the shields of the pipelines must be made in a clear, well-defined font and must not contain unnecessary data, little-used terms and incomprehensible abbreviations. The font for inscriptions is recommended to be taken in accordance with GOST 10807-78*.
________________
* On the territory of the Russian Federation, GOST R 52290-2004 applies. - Database manufacturer's note.

It is allowed to designate the type of substance by means of numbers in accordance with Appendix 3.

The designation of the type of substance by means of chemical formulas is not allowed.

26. The direction of the flow of substances transported through pipelines must be indicated by the sharp end of the marking plates or arrows applied directly to the pipelines.

The shape and size of the arrows must match the shape and size of the labels.

27. Marking shields must be of four types:

1 - to indicate the flow moving in both directions;

2 - the same, in the left direction;

3 - the same, in the right direction;

4 - to indicate the place of selection of the transported substance.

28. The dimensions of the marking plates must correspond to those indicated in Fig. 3 and in Table 6.

Damn.3. - Dimensions of labels

Table 6

Size options

Letter height

one line

two lines

29. Size options for labels, inscriptions and warning signs should be used mainly:

1 - in laboratories;

2 and 3 - in industrial premises;

4 and 5 - on outdoor installations and outdoor main routes.

30. When attaching them to pipelines, warning signs should be placed together with marking plates.

31. The height of markings on pipelines should be taken depending on the outer diameter of the pipeline in accordance with Figure 4 and Table 7.

Damn.4. - Height of markings on pipelines

Table 7

Size options

Outside diameter

Letter height

One line

Two lines

81 to 160

161 to 220

221 to 300

The color of markings and arrows indicating the direction of flow applied to pipelines and marking plates should be white or black, taking into account the greatest contrast with the main color of the pipelines.

The color of the inscriptions when applied against the background of identification coloring is taken:

white - on a green, red and brown background;

black - on a blue, yellow, orange, purple and gray background.

32. The size of labels, inscriptions and warning signs should be selected depending on the distance from which they should be perceived by personnel associated with the operation of pipelines in accordance with Figure 5 and Table 8.

Damn.5. - Size of labels, inscriptions and warning signs

Table 8

Distance from the observer in m

6 to 12

12 to 18

18 to 24

Over 24

33. Paint and varnish coatings for identification painting, marking plates and warning signs must be carried out in accordance with the current standards for paintwork materials and coatings, depending on the material of pipelines or the insulation protecting them and operating conditions, as well as the cost of paint and varnish coatings and the technology of their application.

34. Paints and varnishes used for identification painting, marking plates and warning signs must meet the requirements of the relevant standards, as well as technical documentation approved in the prescribed manner.

35. When preparing surfaces for painting, applying and drying paint and varnish coatings, the safety regulations and fire prevention measures provided for by the current fire regulations and rules must be observed.

36. In heated and ventilated industrial premises without aggressive environments, it is recommended to carry out the identification coloring of pipelines, marking plates and warning signs with pentaphthalic enamels of grades PF-115 according to GOST 6465-76, PF-133 according to GOST 926-82 and other brands according to the technical documentation approved according to established order.

It is recommended to paint fire-fighting pipelines and equipment with red enamel according to the technical documentation approved in the prescribed manner.

37. Identification colors and signal colors are allowed to be accepted in accordance with the following standards of the color standard card index: green N 343-344; red N 10-11; blue N 423-424; yellow N 205-206; orange N 101-102; violet N 505-506; brown N 647-648; gray N 894-895. The required shades of purple and brown in accordance with the samples of Table 1 can be obtained by adding white paint.

38. The identification coloring of pipelines and the color finish of marking plates and warning signs should be periodically renewed, taking into account the provision of clear visibility of colors, images and inscriptions. The coloring should be even, without streaks, wrinkles, spots and should not peel off.

39. Marking boards, inscriptions and warning signs should be located taking into account local conditions at the most critical communication points (at branches, at junctions, at points of selection, at valves, gate valves, valves, gates, control devices, at places where pipelines pass through walls , partitions, ceilings, at inputs and outputs from industrial buildings, etc.).

Marking plates, warning signs and inscriptions on pipelines should be located in well-lit places or illuminated to ensure their clear visibility, while light sources should not obscure the images and inscriptions, as well as dazzle personnel when observing them.

It is recommended to take the lowest illumination at critical communication points with marking plates, inscriptions and warning signs in them at 150 lux with fluorescent lamps and 50 lux with incandescent lamps.

40. In all industrial premises where there are pipelines, in places that are well accessible for viewing, identification coloring schemes for communications should be hung out with a decoding of the distinctive colors, warning signs and digital designations adopted for marking pipelines.

ATTACHMENT 1

ATTACHMENT 1

distinctive color

Chromaticity coordinates
(for source C)

Reflection coefficient, %

y>0.1x+0.412

y>2.8x-0.552
y<0,474-0,1x
x>0.357-0.15y

at<0,290+0,08x

y>0.920-x

y>0.559-0.394x

y>0.316

y<0,550-x

y<0,64x+0,118

y>0.994-3x

y>0.94x+0.024

y>0.084-1.07x

y>0.77x+0.075

y<0,823-0,94x

y

Orange

at<0,204+0,362x

x>0.669-0.26y

Violet

y<0,17x+0,223

y>0.25x+0.185

y>7x-1.854

Brown

x>0.545-0.35y

y>0.19x+0.257

x<0,588-0,25y

y<0,39x+0,195


APPENDIX 2


signal color

Chromaticity coordinates
(for source C)

Reflection coefficient, %

y<0,290+0,080x

y>0.920-x
y>0.559-0.394x
y>0.316

x>0.048+0.827y

y>0.120+0.632x

y>0.887-x

x>0.526-0.683y

x<0,410-0,317y

y>0.282+0.396x

y<0,547-0,394x

APPENDIX 3

Numerical designations

The substance being transported. Name

Water

drinking

technical

hot (water supply)

hot (heating)

nutritious

reserve

reserve

condensate

other types of water

waste, waste

Steam

low pressure (up to 2 kgf/cm)

saturated

overheated

heating

wet (juice)

selective

reserve

vacuum

other types of steam

spent

Air

atmospheric

conditioned

circulation

hot

compressed

pneumatic transport

oxygen

vacuum

other types of air

spent

combustible gases

luminous

generator

acetylene

ammonia

hydrogen and gases containing it

hydrocarbons and their derivatives

carbon monoxide and gases containing it

reserve

other types of combustible gases

waste combustible gases

Non-flammable gases

nitrogen and gases containing it

reserve

chlorine and gases containing it

carbon dioxide and gases containing it

inert gases

sulfur dioxide and gases containing it

reserve

reserve

other types of non-flammable gases

waste non-combustible gases

acids
sulfuric
hydrochloric
nitric
reserve
inorganic acids and their solutions
organic acids and their solutions
acid salt solutions
reserve
other acid reaction liquids
waste acids and acidic effluents (at pH<6,5)
alkalis

sodium

potash

calcareous

lime water

inorganic alkalis and their solutions

organic alkalis and their solutions

reserve

reserve

other alkaline liquids

spent alkalis and alkaline effluents (рН>8.5)

Flammable liquids

category A fluids (<28 °С)

category B liquids (>28 °С<120 °С)*

_______________
* Corresponds to the original. - Database manufacturer's note.

category B fluids (> 120 °C)

lubricating oils

other organic flammable liquids

explosive liquids

reserve

reserve

other flammable liquids

combustible drains

Non-flammable liquids

liquid food products

aqueous solutions (neutral)

other solutions (neutral)

aqueous suspensions

other suspensions

emulsions

reserve

reserve

other non-flammable liquids

non-combustible drains (neutral)

Other substances

powder materials

bulk materials granular

mixtures of solid materials with air

water pulps

pulps of other liquids

reserve

reserve

reserve

waste hard materials

Note. If necessary, each of the subgroups can be divided into ten smaller subdivisions, indicated by the third character of the digital designation (for example, in the enlarged group 4 "Combustible gases" as part of subgroup 6 "Hydrocarbons and their derivatives", ethylene can be distinguished by the third character - 4.61 ).

REFERENCE APPENDIX TO GOST 14202-69. Examples of performing identification painting of pipelines

Examples of performing identification painting of pipelines

Sulphuric acid
Potash alkalis
Hot water for water supply
Superheated steam 450 °C


Compressed air
Leaded gasoline
Ethylene
air vacuum
atmospheric air
Gas outlet line

Water for fire fighting

Note: On hot water and leaded petrol pipes, the inscriptions on the distinctive belts must be white.